Hi,
Test is acceptable as the highest point is witnessed for the required pressure, however please cross check once again for the difference in the highest level to the lowest level and the difference in pressure in terms of Mtr of H2O
Test is acceptable as the highest point is witnessed for the required pressure, however please cross check once again for the difference in the highest level to the lowest level and the difference in pressure in terms of Mtr of H2O
Thanks & Regards,
Lakshman kumar B
+91 9440031459.
On Sat, 2 Jul 2022 at 19:50, Manikandan J <mechmani22@gmail.com> wrote:
Dear All,--We have conducted a hydro test of Piping Spools (14'' Pipe x 12 Mtr Long),we have faced Gauge pressure difference at Higher and lower end.Test Pressure Required : 283 PSIGLower End : 290 PSIGHigher End : 283 PSIGKindly provide what is acceptable pressure difference between lower and higher end.Regards,Pradeepan.
https://materials-welding.blogspot.com/
https://www.linkedin.com/groups/122787
---
You received this message because you are subscribed to the Google Groups "Materials & Welding" group.
To unsubscribe from this group and stop receiving emails from it, send an email to materials-welding+unsubscribe@googlegroups.com.
To view this discussion on the web visit https://groups.google.com/d/msgid/materials-welding/CAPdGVmOG_p74j5MnzJ0ELbmDWCa7gnB0e2%2B13KP1B7TTv3EKdA%40mail.gmail.com.
https://materials-welding.blogspot.com/
https://www.linkedin.com/groups/122787
---
You received this message because you are subscribed to the Google Groups "Materials & Welding" group.
To unsubscribe from this group and stop receiving emails from it, send an email to materials-welding+unsubscribe@googlegroups.com.
To view this discussion on the web visit https://groups.google.com/d/msgid/materials-welding/CAO-dY%3Dha8-EfhOGkq0%3DEB3oZih%2BcXf86ogYzt8iWXpt1%2B0hshA%40mail.gmail.com.
No comments:
Post a Comment