Not a good idea. Not only is 91 in the as welded condition rather brittle but it has been shown to be subject to stress corrosion cracking in the presence of water (condensation, dew, rain, etc.). You can find recommendations sprinkled throughout open literature that discuss the need to keep as welded 91 warm and dry between welding and PWHT. (A tedious Google search should reveal at least four good references – a task left to you). There have been several 91 failures traced back to SCC due to improper handling of 91 in the as welded condition. Some recommendations not only restrict storage conditions but also time duration.
As previously pointed out, all ASME codes require PWHT for all welded 91 without any exemptions.
John
From: materials-welding@googlegroups.com [mailto:materials-welding@googlegroups.com] On Behalf Of Mohamed Farook
Sent: Sunday, August 29, 2010 11:00 PM
To: materials-welding@googlegroups.com
Subject: [MW:6769] Any WPS for P91 Material without PWHT
Dear friends,
Greetings to all,
Please advise me if you have WPS for P91 material without PWHT….
PWHT is time consuming..
Thanks and Regards,
asfaruk
--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding-unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.