-- Where it is mentioned Base metal thick to be considered??
Example:
your thickness is 8mm means width across the notch is less than 80% so you prefer to have subsized 5mm
New sub sized is ==10x5x55
Required sized is ==10x10x55
now temperature reduction is == -20-11.1== -31.1C and
Charpy energy if Original was 27J then new one as per A370 table-9 is 14J.
Hope this will clear.!!
On Saturday, August 17, 2013 11:35:48 AM UTC+3, nguyen tuan wrote:
Dear Experts
I have question about using sub-sized specimen for CVN test
Testing temperature following specification is -20oc ,Plate thickness is 8mm and specimen sized is 10x5
My question How much temperature will apply for testing (AWS D1.1)
"4.36.7 When sub-sized specimens are required, and the
width of the specimen across the notch is less than 80%
of the base metal thickness, the test temperature shall be
reduced in conformance with Table 4.15, unless otherwise
specified in the contract documents
Thanks in advance
Tuan
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding+unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
http://www.linkedin.com/groups/MaterialsWelding-122787?home=&gid=122787&trk=anet_ug_hm
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.
---
You received this message because you are subscribed to the Google Groups "Materials & Welding" group.
To unsubscribe from this group and stop receiving emails from it, send an email to materials-welding+unsubscribe@googlegroups.com.
For more options, visit https://groups.google.com/groups/opt_out.
No comments:
Post a Comment