[MW:19127] Re: Presuure test with Hydraulic Oil.

In constant temperature pressure drop means possible air entrapment in the piping system.  
 
On Monday, October 21, 2013 8:54:17 AM UTC+4, Airon wrote:
Dear Folks,

Been doing pressure test  (different pressures ranging 450 - 7500 psi)  for Hydraulic piping (18-30 mm dia). 
Never had a satisfactory graph. 
Theres a sudden initial drop (mostly) or rise after pressuring. 
During holding time the rise or drop in pressure relative to the atmospheric temperature variation is too much. 
Tried the same test early morning , midnight mid noon and all different times, results are weird graphs.
Subcontractor is not giving a convincing explanation and insists its a normal thing for hydraulic pressure tests. 

Is it normal?
does anyone else have similar experiences or any presentable explanations?

Regards

Airon

--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding+unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
http://www.linkedin.com/groups/MaterialsWelding-122787?home=&gid=122787&trk=anet_ug_hm
 
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.
---
You received this message because you are subscribed to the Google Groups "Materials & Welding" group.
To unsubscribe from this group and stop receiving emails from it, send an email to materials-welding+unsubscribe@googlegroups.com.
For more options, visit https://groups.google.com/groups/opt_out.

No comments:

[MW:34820] RE: 34813] Clarification in Rate of heating and cooling.

Hello,   Please see the response below.   Regards.   P. Goswami, P. Eng, IWE.   From: materials-welding@googlegroups.com <materials-weld...