as per SSPC PA2 we can acept 80-120%, but in your case even you are
getting average 70 microns as per SSPC PA2 it is acceptable, but as a
good workmanship how can you accept a reading of 15, 30, 50 microns.
so for better corrosion protection and good workmanship it should be
rejected.
Thanks.
Haseeb
On Oct 2, 11:37 pm, manoj john <manojac...@gmail.com> wrote:
> Dear All,
>
> Can anybody give the acceptance and rejection criteria as per SSPC PA2. I
> have applied primer to the shell surface of storage tank. The minimum DFT
> required is 75 micron. The actual average DFT is 70 micron and above but
> at some spot I got 15, 30 , 40 microns. Is it acceptable the total area is
> 2500 M2.
>
> I have taken 5 spot reading in 100 Sqft and each spot is the average of
> three single reading, in the single reading i am getting 15, 30, 40 microns
> but average spot reading is above 70 microns.
>
> Thanks in advance
> Manoj John.
--