[MW:12617] Re: DFT ACCEPTANCE AND REJECTION OF PAINTING.

Dear John,

as per SSPC PA2 we can acept 80-120%, but in your case even you are
getting average 70 microns as per SSPC PA2 it is acceptable, but as a
good workmanship how can you accept a reading of 15, 30, 50 microns.
so for better corrosion protection and good workmanship it should be
rejected.

Thanks.

Haseeb

On Oct 2, 11:37 pm, manoj john <manojac...@gmail.com> wrote:
> Dear All,
>
> Can anybody give the acceptance and rejection criteria as per SSPC PA2.  I
> have applied primer to the shell surface of storage tank.  The minimum DFT
> required is 75 micron.  The actual average DFT is  70 micron and above but
> at some spot I got 15, 30 , 40 microns. Is it acceptable the total area is
>  2500 M2.
>
> I have taken 5 spot reading in 100 Sqft and each spot is the average of
> three single reading, in the single reading i am getting 15, 30, 40 microns
> but average spot reading is above 70 microns.
>
> Thanks in advance
> Manoj John.

--