is it B31.1 or B31.3 you are asking? generally it is 20% for category M fluid in B31.3, but project specs may increase up to 100%
-- On 19 December 2016 at 18:48, Zakaria ghrab <zakaria.ghrab@gmail.com> wrote:
Dear Expert,Could you please advise for applicable code for AMMONIA piping (Toxic) in power plant.The issue is that according B31.1 only Visual test is required (according table 136.4).Due to Toxic fluid service , we think it's resonable to extend NDE scope but we need some reference from ASME;There're some ASME piping code for this type of piping ? or other suggestions from your part.Thank you.--
http://www.linkedin.com/groups/MaterialsWelding-122787?home=&gid=122787&trk=anet_ug_hm
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.
---
You received this message because you are subscribed to the Google Groups "Materials & Welding" group.
To unsubscribe from this group and stop receiving emails from it, send an email to materials-welding+unsubscribe@googlegroups.com.
To post to this group, send email to materials-welding@googlegroups.com.
To view this discussion on the web visit https://groups.google.com/d/msgid/materials-welding/CADxVubkZ9jfJ2VzBQ%3Dv96eUSZx3et_UgtdJ-_%2B-wV7DrPwbq8g%40mail.gmail.com.