RE: [MW:32571] Flushing & Cleaning Pressure for piping (Applicable code ASME B31.3 )

Dear Zafar, 

Here my recommendations:
Define the schedule of the pipe, define the length of the span for the flushing, and define the test time. Secure the pipe anchors and supports. Check that it does not generate induced vibration towards static equipment nozzles, as it can generate cracking of the weld.
And most of all, be cautious.

Regards, 
Ramon Briceno 




De: materials-welding@googlegroups.com <materials-welding@googlegroups.com> en nombre de Chaudhary Zafar Iqbal <chzaiqbal88@gmail.com>
Enviado: jueves, 21 de octubre de 2021 4:30 a. m.
Para: materials-welding@googlegroups.com <materials-welding@googlegroups.com>
Asunto: [MW:32570] Flushing & Cleaning Pressure for piping (Applicable code ASME B31.3 )
 
Respected Experts ,

Good Day !

Design Pressure :3.5 Bar & Test Pressure as per isometric dwgs : 5.5 Bar 

Test Medium:Water 

operating condition :
Pressure : 0.4 Bar 
Temperature : AMB 

Pipe Size & material  : 6'' A 53 Gr B Seamless 

My Question : is there any restriction in code to limits the test pressure during flushing with water as  our test pressure will be 7 BAR for flushing and also we need to report the same readings in report .

PIPING SYSTEM – FLUSHING AND TESTING


Report No.:

 

Item

Description of Check

Sub Contr.

Contractor

Company

Sign

Date

Sign

Date

Sign

Date

01

Limits of test in accordance with the scope listed on the attached test index and marked-up P&ID's

 

 

 

 

 

 

02

System prepared for flushing in accordance with the approved procedure.

 

 

 

 

 

 

03

Flushing completed in accordance with the approved procedure

 

 

 

 

 

 

04

System prepared for testing in accordance with the approved procedure

 

 

 

 

 

 

05

System tested in accordance with the approved procedure. (Note 1)

 

 

 

 

 

 

 

Test Results and Readings

Test pressure at start

 

Bar G

Ambient temperature at start

 

oC

Start date and time

 

Date and Time

Test pressure at end

 

Bar G

Ambient temperature at end

 

oC

End date and time

 

Date and Time

Test duration

 

Hours

Tested by contractor

 

Name and Signature

Test witnessed by Company (Note 2)

 

Name and Signature






Best Regards,
Zafar 
M:00966544639978

--
https://materials-welding.blogspot.com/
https://www.linkedin.com/groups/122787
---
You received this message because you are subscribed to the Google Groups "Materials & Welding" group.
To unsubscribe from this group and stop receiving emails from it, send an email to materials-welding+unsubscribe@googlegroups.com.
To view this discussion on the web visit https://groups.google.com/d/msgid/materials-welding/CAP9k9XcJc%3DZ8C6JrVdk1K1v9iN06t_NeBZrqkfk6OehQ%2BCfdng%40mail.gmail.com.

Comments

Popular posts from this blog

Re: [MW:34105] SA266 GR4N 4 Cycle SPWHT

Hi,  You are correct, Minimum refers to the one cycle for which this part will expose until final work shop PWHT. hence mill test certificate shall include this.  Max. SPWHT, refers to additional cycles of heat treatment that are reserved for future repairs during equipment lifetime.  Again, these simulated no. Of cycles shall be specified in MTC.  The idea is we need to make sure that steel mechanical properties are not compromised upon exposure to multiple repairs (i e 4 cycles in your case).  One could say, if steel is subjected to 4 cycles and is ok, then it should by defacto be good for one cycle, yet, this is wrong assumption cause mechanical problems and microstructure of materials varies accordingly based on no. Of cycles for which material will expose. This is apparent in alloy steel and especially for impact test values as an example.  In your case, this forged CS with properties before PWHT can be understood to be " as forged" condition (i.e. Wit...

Materails FAQs

Q: What are equivalents for standard Q 235 B (and Q 235 A) for U-channels? (asked by: boris.vielhaber@vait.com) A: DIN Nr. = 2393 T.2, 2394 T.2, EN 10025 W. Nr. DIN 17007 = 1.0038 Design DIN 17006 = RSt 37-2, S235JRG2 (Fe 360 B) Q: What is St DIN 2391 BK material? (asked by: dmcandrews@automaticstamp.com) A: Precision steel tubes, cold-finished/hard. Q: What is C.D.W. Boiler Tube? (asked by: montydude123@yahoo.com) A: Cold Drawn Welded Boiler Tube. Q: WHAT IS W.Nr. 1.4301? PLS TELL US IN EASY LANGUAGUE (asked...

Heat tint (temper) colours on stainless steel surfaces heated in air // Heat tint

Introduction The colour formed when stainless steel is heated, either in a furnace application or in the heat affected zone of welds, is dependent on several factors that are related to the oxidation resistance of the steel. The heat tint or temper colour formed is caused by the progressive thickening of the surface oxide layer and so, as temperature is increased, the colours change.   Oxidation resistance of stainless steels However, there are several factors that affect the degree of colour change and so there is no a single table of colour and temperature that represents all cases. The colours formed can only be used as an indication of the temperature to which the steel has been heated. Factors affecting the heat tint colours formed Steel composition The chromium content is the most important single factor affecting oxidation resistance. The higher the chromium, the more heat resistant the steel and so the development of the heat tint colou...