I think the set pressure is 3% above the test pressure.....Shank

shailesh dave <snd2988@yahoo.com> wrote:
DEAR Mr. RAGHURAM,
 
THANKS FOR THE REPLY.
 
REGARDS,
 
S.N.DAVE

Raghuram Bathula <raghurambathula@gmail.com> wrote:

When conditions require that a pressure test will be maintained for a
period of time during which the testing medium in the system would be
subject to thermal expansion, provision should be made for relief of
excess pressure.

I have no idea about any code requirement but normal practice as per
my experience for Valve Setting Pressure is Test pressure plus
lesser of 10 psi (0.69 Bar a) or 7% of the test pressure



> From: shailesh dave [mailto:snd2...@yahoo.com]
> Sent: Wednesday, January 30, 2008 1:46 PM
> To: materials-welding@googlegroups.com
> Subject: Re: [MW:537] Re: 533] Filler metal for P 11 (O/L SS 347) to P8
>
> Dear Members,
>
> Can anybody tell me at what pressure of hydrotest be safety relief valve set. What is the reference code.
>
> Regards,
>
> S.N.Dave
>
> QA/QC Manager
>
> ---------------------------------
> Never miss a thing. Make Yahoo your homepage.

Be a better friend, newshound, and know-it-all with Yahoo! Mobile. Try it now.
Looking for last minute shopping deals?
Find them fast with Yahoo! Search. --~--~---------~--~----~------------~-------~--~----~
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding-unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
-~----------~----~----~----~------~----~------~--~---

No comments:

[MW:35346] Cast-iron welding

Any advice for cast iron welding Sent from Yahoo Mail for iPhone