Re: [MW:14213] API 650 - Vacuum box test Vs PT/MT(Penetrant Test/MPI)

Dear

In my experience , it seems CHEAPER AND MORE EFFECTIVE FINDINGS WITHOUT MORE CONCENTRATED VISUAL INSPECTION. imagine how much penetrant and developer use for a small tank. same thing in MT also. material which using for test is costly. but If we use Vacuum box testing, at least we can cover nearly 1 meter length and minimum 5 inch width both sides of weld. and if a hole opening o both side in the weld( even in multi run weld)  air bubbles comes continuously, it is visible easily in sunlight glare also.not expensive with compare to  other PT & MT. normal soap water or any approved liquid using for the test. that is not much expensive.

On Mon, May 7, 2012 at 4:21 PM, M S <striarc@gmail.com> wrote:

Please provide technical support:-

What is the difference between Vacuum box test(for leak detection) and PT(for surface discontinuity detection)?

PT can detect all the surface discontinuity as well and MT can detect surface and slightly subsurface discontinuity also, but why API 650 prefers Vacuum box test instead of PT for Carbon steel-tank bottom plate welding?

--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding+unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.



--
Thanks & Regards

PRADEEPKUMAR HORMIS
Mob: +91-0-9496754791




--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding+unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.

No comments:

Re: [MW:34913] Filler wire

E71T-1C  is Charpy Impact tested at -20degC E71T-1CJ is Charpy impact tested at -40degC. AWS Classification for FCAW is only a supplementary...