[MW:12617] Re: DFT ACCEPTANCE AND REJECTION OF PAINTING.

Dear John,

as per SSPC PA2 we can acept 80-120%, but in your case even you are
getting average 70 microns as per SSPC PA2 it is acceptable, but as a
good workmanship how can you accept a reading of 15, 30, 50 microns.
so for better corrosion protection and good workmanship it should be
rejected.

Thanks.

Haseeb

On Oct 2, 11:37 pm, manoj john <manojac...@gmail.com> wrote:
> Dear All,
>
> Can anybody give the acceptance and rejection criteria as per SSPC PA2.  I
> have applied primer to the shell surface of storage tank.  The minimum DFT
> required is 75 micron.  The actual average DFT is  70 micron and above but
> at some spot I got 15, 30 , 40 microns. Is it acceptable the total area is
>  2500 M2.
>
> I have taken 5 spot reading in 100 Sqft and each spot is the average of
> three single reading, in the single reading i am getting 15, 30, 40 microns
> but average spot reading is above 70 microns.
>
> Thanks in advance
> Manoj John.

--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding+unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.

No comments:

[MW:34866] Presentation for WPS ,PQR AND WPQ as per ASME Sec IX in power point

Dear Experts.        If anyone having presentation of WPS,PQR and WPQ  as per ASME  SEC.IX  in power point then please share . Regards Sanja...