Re: [MW:12138] API storage tank settlement tolerance.

Manoj,
You need to see API 650 11th edition 7.3.6.6

7.3.6.6 If settlement measurements are specified by the Purchaser, any differential settlement greater than 13 mm per 10 m
(1/2 in. per 32 ft) of circumference or a uniform settlement over 50 mm (2 in.) shall be reported to the Purchaser for evaluation.
Filling of the tank shall be stopped until cleared by the Purchaser.

Regards,
Usman

On Sat, Aug 6, 2011 at 3:16 PM, manoj john <manojacgnr@gmail.com> wrote:
Dear All,

I have one storage tank to erect at site as per API 650.  The size of the tank is 54 meter diameter and during water fill up test we have to measure settlement.  Can any body give me information about tank settlement tolerance and in which standard it is specified.

Thanks,
Regards.
Manoj

--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding+unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.

--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding+unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.

No comments:

[MW:34820] RE: 34813] Clarification in Rate of heating and cooling.

Hello,   Please see the response below.   Regards.   P. Goswami, P. Eng, IWE.   From: materials-welding@googlegroups.com <materials-weld...