Re: [MW:11849] T91+SS welding

Dear S.Nareshkumar:

Tricky Subject...
Study the attached file
In page 3, you sea two figures (left diagram) that show the required
Heat treatment and Temp. control during welding for P91 (that is same
as T91) and you will realize that T91 definitely needs to be post-weld
heat treated in 760 degrees...
This is bad for 304, very bad...

BUT

Please give me more details on the location of the joint and the
service conditions.
And why are you welding these two materials together...?
Couldn't you use flanged joints instead...?

I think eventually, it's easier to change the design (if possible)...

Anyway, please send more details...!!!

Regards
Ramin Kondori
IWE AT 0070

----------------------------------------------------------------------------------------------
*********************************************************************************


On 7/18/11, Naresh Kumar <snareshkumar30@yahoo.com> wrote:
> Dear friends,
> Any one guide me whether SA213 T91+SA213 TP304 welding PWHT require or not.
> Filler wire used:
> ER NiCr3
>
> Regards,
> S.Nareshkumar
>
> --
> To post to this group, send email to materials-welding@googlegroups.com
> To unsubscribe from this group, send email to
> materials-welding+unsubscribe@googlegroups.com
> For more options, visit this group's bolg at
> http://materials-welding.blogspot.com/
> The views expressed/exchnaged in this group are members personel views and
> meant for educational purposes only, Users must take their own decisions
> w.r.t. applicable code/standard/contract documents.
>


--
Ramin Kondori
* QC/Welding Engineer *
* IWE AT 0070*
**

--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding+unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.

No comments:

Re: [MW:34913] Filler wire

E71T-1C  is Charpy Impact tested at -20degC E71T-1CJ is Charpy impact tested at -40degC. AWS Classification for FCAW is only a supplementary...