Monday, April 19, 2010

[MW:4882] RE: 4825] ASME B 31.1 welded pipe in boiler external piping

Hello Vinayak,
 
Yes you are correct ASME 31.1 only allows SMLS pipe for boiler external piping, mentioned plate materials are for manufacturing of other items.
 
Kind regards

Rahul



From: materials-welding@googlegroups.com [mailto:materials-welding@googlegroups.com] On Behalf Of Nivendkar Vinayak (Mumbai - Piping)
Sent: vrijdag 16 april 2010 12:13
To: materials-welding@googlegroups.com
Subject: [MW:4825] ASME B 31.1 welded pipe in boiler external piping

Dear all,

 

As per ASME B 31.1 Anex –A Table A-1 note 1 , it seems that we could not used welded pipe A 671 , A672 for pressure retaining parts of external boiler piping .

But for the same time Plate material A515,A516 is allowed.

 

Now my query “are welded pipes are not allowed for boiler external piping   as per ASME B 31.1.

 

Kindly reply.

 

Regards,

Vinayak Nivendkar

 



____________________________________________________________________________
This email has been scanned for Viruses and Spam. For more information
please contact your local Business Unit Information Security representative.
____________________________________________________________________________

--
To post to this group, send email to materials-welding@googlegroups.com
To unsubscribe from this group, send email to materials-welding-unsubscribe@googlegroups.com
For more options, visit this group's bolg at http://materials-welding.blogspot.com/
The views expressed/exchnaged in this group are members personel views and meant for educational purposes only, Users must take their own decisions w.r.t. applicable code/standard/contract documents.

No comments:

Re: [MW:34832] Inquiry about Single Bevel with Back Grinding

Dear Uday, As per your question that one is called with backing only,Simple both side you are welding it is backing with strip or without st...